The Effect of Pressure Difference Control on Hydraulic Stability in a Variable Flow Air Conditioning System
Abstract
This paper analyzes the effects of different pressure difference control methods on hydraulic stability in a variable flow air conditioning system when it is applied to different air conditioning water systems. According to control method and water system, it can be divided into direct return system pass-by control, direct return system terminal control, reversed return system pass-by control and reversed return system terminal control. The results indicate that reversed return system terminal control has the best hydraulic stability.
Citation
Zhang, Z.; Fu, Y.; Chen, Y. (2006). The Effect of Pressure Difference Control on Hydraulic Stability in a Variable Flow Air Conditioning System. Energy Systems Laboratory (http://esl.tamu.edu); Texas A&M University (http://www.tamu.edu). Available electronically from https : / /hdl .handle .net /1969 .1 /5306.